The SIVACON 8PT low voltage switchboard panel is the solution for building and industrial engineering. The wide range of possible module combinations allows the switchboard to be ideally adjusted to meet every demand with maximum current to 7400A

Product Details

Siemens SIVACON 8PT Low Voltage Switchboard Panel

The SIVACON 8PT low voltage switchboard panel is the solution for building and industrial engineering. The wide range of possible module combinations allows the switchboard to be ideally adjusted to meet every demand with maximum current to 7400A.

 

Features

●Type-tested Standard modules(TTA)

Standardized busbar position at the top of the cubicle

3- and 4-pole busbar system up to 7400A

Rated peak withstand current lpk up to 375KA

Deep switchgear compartment for universal installation

Modular structure of device compartment

Single-front and back-to-back installation

Cable lead-in from above or below

Cable connection from the front or rear

 

Benefits

Modular technology makes it possible to adopt SIVACON optimally to all requirements

Standard horizontal busbar position at the top of the cubicle

Any components can be installed in the device compartments regardless of the busbar position and cubicle depth

Requirement-oriented compartmentalization of functional units(Form 1 to Form 4 according to IEC 60439-1)

Deep device compartments optimum adaptation to space conditions

Wall-mounted or free-standing

Cables and busbar may be connected optionally from above of busbar

 

Application

The SIVACON 8PT low voltage switchboard panel for all application the low-voltage network

 

Type Testing

Verification of temperature rise limits by test

Verification of dielectric properties by test

Verification of short-circuit withstand strength by test

Verification of the effective connection between the expose conductive parts of the assembly and the protective circuit by inspection or resistance measurement

Verification of the short-circuit withstand strength of the protective circuit by test

Verification of the clearances and creepage distance

Verification of mechanical operation

Verification of the degree of protection


Technical Parameters

Standard and Specification

Type-tested low voltage and control gear assembly(TTA)

IEC60439-1, DINEN60439-1(VDE0660 Part 500)

Testing of  response to internal faults(arcing faults)

IEC61641, VDE0660 Part 500

Creepage Distance & Clearances

Rated impulse withstand voltageUimp

8KV

Overvoltage category

III

Pollution level

3

Rated Insulation Voltage (Ui)


1000V

Rated Operational Voltage (Ue)


690V

Rated Current (in) Busbar (3-pole & 4-pole)

Main horizontal busbar

Rated current

≤7400A

Rated peak withstand current (Ipk)

≤375KA

Rated short time withstand current (Icw)

≤150KA, 1S
  ≤120KA, 3S

Vertical busbar for circuit breakers

Rated current

≤6300A

Rated peak withstand current (Ipk)

≤250KA

Rated short time withstand current (Icw)

≤100KA, 1S
  ≤80KA, 3S

Vertical busbar for fixed-mounted design

Rated current

≤1400A

Rated peak withstand current (Ipk)

≤163KA

Rated short time withstand current (Icw)

≤65KA, 1S
  ≤50KA, 3S

Vertical busbars for withdrawable-unit design

Rated current

≤1200A

Rated peak withstand current (Ipk)

≤163KA

Rated short time withstand current (Icw)

≤65KA, 1S
  ≤50KA, 3S

Switchgear Rated Current


Circuit Breakers

≤6300A

Outgoing   feeders

≤630A

Internal Separation

Form 1 to Form 4

IEC 60439-1, Section 7.7, DIN EN 60439-1

Surface Treatment

Frame Parts

Galvanized/powder-coated/wet-painted

Enclosure

Galvanized/powder-coated/wet-painted

Doors

Galvanized/wet-painted

Degree of Protection

Comply IEC 60529, EN 60529

IP 30 to IP 54

Dimensions


Height: 2200, 2600 mm (with busbar top unit)

Width: 600, 800, 1000, 1200 mm

Depth: 600, 800, 1000, 1200 mm