Home > Knowledge > Content

Schneider WS-G12-40.5kV AC Metal Clad SF6 Insulated Electric Switchgear dimension and weight

Jun 02, 2017

 

Schneider WS-G12-40.5kV AC Metal Clad SF6 Insulated Electric Switchgear dimension and weight


Single busbar cabinet dimension

Rated   voltage

kV

12-36

40.5

Rated   current

A

800-1600

2000

2500

800-1600

2000

2500

Cabinet   dimension

Width  

mm

Incoming/outgoing   line, busbar lift

600,800

600,800

900

600

600

900

Busbar   contact scheme

800

800

1000

800

800

1000

Busbar   isolation scheme

600

600

600

600

600

600

Depth

mm

1340

1380

1380

1340

1380

1380

Height  

mm

2400

2400

2400

2400

2400

2400

Note: 1. If add cover plate at the rear of cabinet, the depth of cabinet is 1500mm.

          2. If add the height of LV chamber to 1200mm, the height of cabinet will be 2780mm.


Double busbar cabinet dimension

Rated   voltage

kV

12-36

40.5

Rated   current

A

800-1600

2000

2500

800-1600

2000

2500

Cabinet   dimension

Width  

mm

Incoming/outgoing   line, busbar lift

600,800

600,800

900

600

600

900

Busbar   contact scheme

800

800

1000

800

800

1000

Busbar   isolation scheme

600

600

1000

600

600

1000

Depth

mm

1700

1970

1970

1700

1970

1970

Height  

mm

2400

2400

2400

2400

2400

2400

Note: If add the height of LV chamber to 1200mm, the height of cabinet will be 2780mm.


Weight of WS-G switchgear

Switchgear  


Weight   (kg)

                                                                             

001.jpg

   

Outgoing   line cabinet

External   conical type cable connection

Internal   conical type cable connection

 

700

 

1000

 

002.jpg

 

incoming   line cabinet

External   conical type cable connection

Internal   conical type cable connection

 

700

 

900

 

003.jpg

 

Busbar   sectional cabinet

1100

Note: PT and LV box are not included in the weight.

If need to install PT and other accessories to busbar side, 50-120kg will be added to the weight of switchgear.