12kv 20kv 15kv 22kv 24kv Electrical Panel Medium Voltage Metal-Clad Switchgear

1. Product name: KYN61-40.5 AC Medium Voltage Metal Clad Industrial Indoor switchgear
2. Major components: CB, disconnecting switch, earthing switch, Instrument, air switches
3. Brief Introduction: Four chambers and FIVE PREVENTIONS INTERLOCK
4. Certification: Test report
5. Rated Voltage:40.5kV,Rated Frequency 50/60Hz,Rated Current:1250,1600A
6. Custom switchgears can be supplied

Product Details
We plan to develop a broader small compression springs, power factor correction capacitor bank, electrical cubicle product layout, and use high-quality products with professional knowledge to provide customers in the industry with more high-quality and effective one-stop product services. With the aim of 'compete with good quality and develop with creativity' and the service principle of 'take customers' demand as orientation', we will earnestly provide qualified products and solutions and good service for domestic and international customers. The mission of our company is to innovate without forgetting environmental protection, to benefit the enterprise without forgetting to benefit customers. Our solutions have national accreditation requirements for qualified, good quality products, affordable value, was welcomed by individuals all over the world. In the era of rapid change, we take advantage of leading technology, advocate the future with science and technology.

KYN61-40.5 AC Medium-Voltage Metal-clad Removable-type Switchgear 

1. General

KYN61-40.5  Removable AC medium voltage Metal clad industrial electrical switchgear (hereinafter referred to as switchgear) is a 40.5kV three-phase AC 50Hz distribution equipment which is applied to the distribution rooms of power plants, power substation and industrial and mining enterprises to receive and distribute power to control, protect and monitor circuit; besides the extensive application in general power system, this switchgear can be used in frequent operation area. This indoor switchgear meets the requirements of GB3906-2006 and IEC62271-200 (AC Metal-enclosed Switchgear and Control Equipment).

2. Mode and Definition

                                         

3. Operational Environment

a. Ambient Temperature: -10℃~+40℃;

b. Altitude: Below 1000m;

c. Relative Humidity: the average not more than 95%, monthly average not more than 90%;

d. Seismic Intensity: less than 8-magnitude

e. It is not applicable to operate in corrosive and combustible gas and water-vapor polluted places. 

4. Technical Parameters

 

Items

Units

Parameters

 

Rated Voltage

kV

40.5

 

Rated Frequency

Hz

50

 

Rated Current

A

1250,1600

 

Rated Closed Current   (Peak)

kV

25,31.5

 

4s Thermal Stability   Current

kV

63,80

 

Rated Dynamic   Current (Peak)

kV

25,31.5

Insulation Level

1min   Power Frequency Withstand Voltage (Effective Value) (Interphase, phase-ground)  

kV

95

Lighting Impulse   Withstand Voltage (Peak)

kV

185

Isolation Break 1min   Power Frequency Withstand Voltage (Effective Value)

kV

115

 

Isolation fracture Lightning   Impulse Withstand Voltage (Peak)

kV

215

 

                                                                                                                       Enclosure Protection Class

 

Shell IP4X,   isolation room IP2X

 

Cabinet Body   Dimension (Width*Depth*Height)

mm

1400×2800×2600   1600×2800×2600(transformer   cabinet used in distribution      substation)


5. Outline Diagram of Electrical Switchboard

    

 

 A.    instrument chamber      B. CB chamber     C. busbar chamber

D. cable chamber                  E. mini busbar chamber

1. Pressure releasing plate    2.  Lifting ring          3. Shutter 

4. CB                                5. Contactor box              6. Secondary plug 

7. Heating device           8. CT        9. Cable            10. Insulation isolation plate

11. Earthing switch        12. Main busbar               13. Branch busbar 

14. Busbar bushing        15. Lightning arrestor      16. Light

 

6.  Ordering instructions

a. Main wiring plan No., single-line system diagram and arrangement diagram;

b. Secondary circuit wiring schematic diagram, terminal arrangement diagram;

c. Type, specification and quantity of electric elements inside switchgear;

d. Detail information should be given when order if the switchgear will be operated in special environment;

e. Type and quantity of accessories and spare parts should be offered if necessary.

 

7. Test report

 

 

 

test7

 

XD HI-TECH, established 2007, is one of the excellent manufacturers in China. Come and find kyn61-40.5 removable ac medium voltage metal clad industrial indoor electrical switchboard/cubicle/switchgear manufacturer from our factory. Coming in high precision, and good performance, our custom products have a wide application field. Welcome to wholesale our quality products and the PDF display is also offered.

Foreign trade has been exported to many countries and regions, and has become one of the important production bases of 12kv 20kv 15kv 22kv 24kv Electrical Panel Medium Voltage Metal-Clad Switchgear export in our country. Welcome to visit our website and do not hesitate to communicate with us. Top quality, timely company and Aggressive cost, all win us a superior fame in xxx field despite the international intense competition.
Hot Tags: removable ac medium voltage metal electrical switchboard China, manufacturers, suppliers, factory, wholesale, design, custom, application, PDF, power factor correction capacitor bank, spring steel, cone shaped spring, expansion spring, spiral torsion spring, transfer switch
Inquiry